Figure 31: Text Detail - Marking Example For Approved Ex I I/O Modules; Table 44: Description Of Marking Example For Approved Ex I I/O Modules - WAGO 750 Manual

Table of Contents

Advertisement

76
Use in Hazardous Environments
Figure 31: Text Detail – Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Table 44: Description of Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Marking
Dust
Ex
nA
[ia IIIC]
IIC
T4
Gc
X
Gases
Ex
nA
[ia Ga]
IIC
T4
Gc
X
Manual
Version 1.0.0
All manuals and user guides at all-guides.com
Description
Explosion protection mark
Type of protection
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
Group
Temperature class
Equipment protection level (EPL)
Symbol used to denote specific conditions of use
Explosion protection mark
Type of protection
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 0
Group
Temperature class
Equipment protection level (EPL)
Symbol used to denote specific conditions of use
WAGO-I/O-SYSTEM 750
750-471 4AI U/I Diff Galv

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-471

Table of Contents