Table of Contents

Advertisement

36
Process Image
Table 21: Signal Types "0 ... 10 V, 0 ... 20 mA" and "4 ... 20 mA" with Status Information in the
Process Image
Measuring range
0 ... 10
V
n.a.
< − 22.0
Neg. sensor overload
n.a.
Wire break
< − 0.5
< − 1.0
Underrange
0
1
2
3
4
5
6
7
8
9
10
Exceeding
> 10.4
Sensor overload
n.a.
1)
Status bits: X: not used, F= error, Ü= overrange
2)
When underrange/overrange limit is ON
3)
When wire break / overload diagnostics is ON
Manual
Version 1.0.0
All manuals and user guides at all-guides.com
0 ... 20
4 ... 20
mA
mA
Measuring value
< − 14.0
0000.0000.0000.0
3)
n.a.
< 1.0
0000.0000.0000.0
3)
< 3.0
0000.0000.0000.0
2)
0
4.0
0000.0000.0000.0
2
5.6
0000.1100.1100.0
4
7.2
0001.1001.1001.1
6
8.8
0010.0110.0110.0
8
10.4
0011.0011.0011.0
10
12.0
0011.1111.1111.1
12
13.6
0100.1100.1100.1
14
15.2
0101.1001.1001.1
16
16.8
0110.0110.0110.0
18
18.4
0111.0011.0011.0
20
20.0
0111.1111.1111.1
2)
0111.1111.1111.1
> 21.0
> 21.0
3)
0111.1111.1111.1
> 22.0
> 22.0
WAGO-I/O-SYSTEM 750
750-471 4AI U/I Diff Galv
Process value
Binary
Hex.
1)
XFÜ
011
0x0003
011
0x0003
011
0x0003
000
0x0000
000
0x0CC8
000
0x1998
000
0x2660
000
0x3330
000
0x3FF8
000
0x4CC8
000
0x5998
000
0x6660
000
0x7330
000
0x7FF8
011
0x7FFB
011
0x7FFB
Status
Error
byte
LED
Dec.
hex.
3
0x50
on
3
0x60
on
3
0x41
on
0
0x00
off
3272
0x00
off
6552
0x00
off
9824
0x00
off
13104
0x00
off
16376
0x00
off
19656
0x00
off
22936
0x00
off
26208
0x00
off
29488
0x00
off
32760
0x00
off
32763
0x42
on
32763
0x50
on

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-471

Table of Contents