Signal Type "Namur Ne43; Table 26: Signal Type "Namur Ne43", Two's Complement - WAGO 750 Manual

Table of Contents

Advertisement

40
Process Image
4.3.1.3

Signal Type "Namur NE43"

Table 26: Signal Type "Namur NE43", Two's Complement

Measuring range [mA]
Namur NE43
< - 14.0 mA
Neg. sensor overload
< 1.0
Wire break
< 3.6
Underrange
3.8
4.0
5.6
7.2
8.8
10.4
12.0
13.6
15.2
16.8
18.4
20.0
20.5
Exceeding
> 21.0
Sensor overload
> 22.0
2)
When underrange/overrange limit is ON
3)
When wire break / overload diagnostics is ON
Manual
Version 1.0.0
All manuals and user guides at all-guides.com
Binary
1111.1110.0111.0011
3)
1111.1110.0111.0011
3)
1111.1110.0111.0011
2)
1111.1110.0111.0011
0000.0000.0000.0000
0000.1100.0110.1001
0001.1000.1100.1010
0010.0101.0011.1100
0011.0001.1010.0110
0011.1110.0000.1111
0100.1010.0111.1000
0101.0110.1110.0010
0110.0011.0100.1011
0110.1111.1011.0100
0111.1100.0001.1110
0111.1111.1111.1111
2)
0111.1111.1111.1111
3)
0111.1111.1111.1111
WAGO-I/O-SYSTEM 750
750-471 4AI U/I Diff Galv
Process value
Hex.
Dec.
0xFE73
− 397
0xFE73
− 397
0xFE73
− 397
0xFE73
− 397
0x0000
0x0C69
3177
0x18CA
6346
0x253C
9532
0x31A6
12710
0x3E0F
15887
0x4A78
19064
0x56E2
22242
0x634B
25419
0x6FB4
28596
0x7C1E
31774
0x7FFF
32767
0x7FFF
32767
0x7FFF
32767
Status
Error
byte hex.
LED
0x50
on
0x60
on
0x41
on
0x00
off
0
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x00
off
0x42
on
0x50
on

Advertisement