ICP DAS USA ZT-2017 User Manual page 125

Table of Contents

Advertisement

A.6 37 (0x25) Reading the Channel Enabled/Disabled Status
Description
This sub-function code is used to read the enabled/disabled status for
each channel of a module.
Request
Byte
Description
00
Address
01
Function Code
Sub-function
02
Code
Response
Byte
Description
00
Address
01
Function Code
Sub-function
02
Code
03
Enabled/Disabled
Status
Error Response
Byte
Description
00
Address
01
Function Code
ICP DAS, ZT-2017 and ZT-2017C AI Series User Manual, Version 1.0.1
Copyright © 2012 by ICP DAS Co., Ltd. All Rights Reserved.
Length Value
1
1 to 247
1
0x46
1
0x25
Length Value
1
1 to 247
1
0x46
1
0x25
1
0x00 to 0xFF. The enabled/disabled status of
each channel, where bit 0 corresponds to
channel 0, and bit 1 corresponds to channel
1, etc. When the bit is 0, it denotes that the
channel is disabled, and 1 denotes that the
channel is enabled.
Length Value
1
1 to 247
1
0xC6
Page 125