Table of Contents

Advertisement

6.2.36 @AARHCi

Description
This command is used to read the status of the high alarm for a specific channel
of a specified module.
Syntax
@AARHCi[CHECKSUM](CR)
@
Delimiter character
AA
The address of the module to be read in hexadecimal format (00 to FF)
RH
The command to read the status of the high alarm
Ci
The channel to be read, zero based
Response
Valid Command
Invalid Command
!
Delimiter character to indicate a valid command
?
Delimiter character to indicate an invalid command
AA
The address of the responding module in hexadecimal format (00 to FF)
(Data) The high latch values for all channels. See Section 4 for details of the
engineering units format.
S
The alarm type:
0: Alarm Disabled
1: Momentary Alarm
2: Latched Alarm
There will be no response if the command syntax is incorrect, there is a
communication error, or there is no module with the specified address.
Example
Command @03HI+09.000C0M
Response
!03
Sets the high alarm limit for channel 0 of module 03 to +09.000 and sets the
alarm type to momentary, and returns a response indicating that the command
ICP DAS, ZT-2017 and ZT-2017C AI Series User Manual, Version 1.0.1
Copyright © 2012 by ICP DAS Co., Ltd. All Rights Reserved.
!AA(Data)S[CHECKSUM](CR)
?AA[CHECKSUM](CR)
Page 95