TM
HRT-711
User's Manual
Version 1.00

Advertisement

Table of Contents
loading

Summary of Contents for ICP DAS USA HRT-711

  • Page 1 HRT-711 User’s Manual Version 1.00...
  • Page 3: Revision History

    Revision History Revision Date Description 1.00 2014/01/21 First revision...
  • Page 5 Preface Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year from the date of delivery to the original purchaser. Warning ICP DAS assumes no liability for damages resulting from the use of this product. ICP DAS reserves the right to change this manual at any time without notice.
  • Page 7: Table Of Contents

    4.2.10 Input Data Area-Default CMD 3 Simple Format Data ..........25 4.2.11 Output Data Area ........................26 4.3 T ............................27 HROUGH SECTION 5- UTILITY ............................28 5.1 .NET F ......................28 RAMEWORK NSTALLATION 5.2 I HRT-711 U ........................29 NSTALL TILITY HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 8 APPENDIX B COMMAND FORMAT ......................52 HART ....................52 HE SIMPLE FORMAT OF COMMAND Command 1:(Read Primary Variable) ..................52 Command 2:(Read P.V. Current and Percentage of Range) ..........52 Command 3:(Read Dynamic Variables and P.V. Current) ............. 52 HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 9: Section 1- Introduction

    Modbus and HART are two kinds of famous protocols and used wildly in the fields of factory and process automation. The HRT-711 module is a Modbus to HART gateway. By using this module, users can integrate their HART devices into Modbus network easily. The below figure 1 shows an application example for the HRT-711 module.
  • Page 10: Specification

    Operating temperature: -25 ~ 75 ºC Storage temperature: -30 ~ 85 ºC Humidity: 5 ~ 95% RH, non-condensing Module 3 x LED indicators ETH LED Network Status HART LED HART Status ERR LED Error HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 11: Section 2- Hardware

    Block Diagram Section 2- Hardware Section 2- Hardware 2.1 Block Diagram 2.2 Pin Assignment LED Status Indicators Ethernet HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 12: Wiring

    In this section, this user’s manual will introduce the wiring for each interface. 2.3.1 RS-232 The RS-232 port of HRT-711 uses a 3-wire communication interface. It needs a unique cable, CA-0910, to wire from screwed terminal block to D-Sub 9pin connector. Users can choose use CA-0910 for RS-232 wiring or directly connecting to D-Sub.
  • Page 13: Hart

    The wiring of HART bus can be devided into two types. One is loop power (Passive Loop), and the other is external power (Active Loop). The following figures show the wiring for the HART bus. HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 14 Section 2- Hardware Wiring HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 15: Ethernet

    Section 2- Hardware 2.3.3 Ethernet The wiring for Ethernet is directly connecting your RJ-45 Ethernet cable to the RJ-45 port on the HRT-711. 2.4 LED Indicators The HRT-711 provides three LED indicators to indicate the module status. The descriptions are shown as follow.
  • Page 16: Jumpers

    1&2 of JP4 is closed, the resistor will connect to HART bus. When the pin 2&3 of JP4 is closed or JP4 without jumper connected, it will disconnect the resistor from HART bus. By default, the pin1&2 of JP4 is closed. Please refer to section 2.3.2. HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 17: Mounting

    Mounting Section 2- Hardware 2.7 Mounting HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 18: Section 3- Hart Introduction

    - 1,200 Hz and 2,200 Hz representing bits 1 and 0, respectively. Sine waves of these two frequencies are superimposed on the direct current (dc) analog signal cables to provide simultaneous analog and digital communications. HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 19: Topology

    7 HART devices simultaneously. If the HART devices in multi-drop mode are more than 7, then users need to disconnect the built-in resistor in HRT-711 (prevent to burn down) and use the external 250 Ohm resistor with 1W.
  • Page 20: Hart Frame

    This byte is used for error status when Bit7 is 1. The status bits are shown as follow Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 Parity Overrun Framing Checksum 0(Reserve RX buffer Overflow Error error Error error overflow (Undefine) HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 21 The contents of the data are decided by HART command number. Every HART frame has a check byte at the last data byte. HART device can detect error Check Byte frame by this byte. HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 22: Section 4- Modbus Communication

    When the HRT-711 module is started, it will perform the Initial mode first and then the Operation mode. (1) When HRT-711 runs in Initial mode, it will execute all initial command and the HART led will flash. (2) When HRT-711 runs in Operation mode, it will execute all polling command automatically and the HART led will always on.
  • Page 23: Input Data Area-Default Cmd 0 Data

    255. 4.2.3 Input Data Area-Default CMD 0 Data The HRT-711 will automatically add two default commands, CMD 0 and CMD 3, when add a HART device. The following table represents the default CMD 0 data Modbus address mapping.
  • Page 24: Input Data Area-Default Cmd 3 Normal Format Data

    Default CMD 0 input data of Module 15 4.2.4 Input Data Area-Default CMD 3 Normal Format Data When configure HRT-711 default CMD 3 to normal format, the data of Modbus address for each HART device is shown as following table.
  • Page 25: Input Data Area-Module Error Record Data

    Default CMD 3 Normal Format Data of Module 15 4.2.5 Input Data Area-Module Error Record Data The HRT-711 records the latest 3 error when HART communication has error. These 3 records are put themodule error record data. The format of each record is shown as following table.
  • Page 26: Input Data Area-User Cmd Error Status

    Reserved 4.2.7 Input Data Area-User CMD Error Status The HRT-711 supports maximum 100 User CMD. The index of the User CMD is from 0 to 99. Each Modbus address represents two User CMD statuses. Ex: If the value is 0x0200 for the MB address 1050, then the low byte of the 1050 is 0x00 and the high byte of the 1050 is 0x02.
  • Page 27: Input Data Area-Module Hardware Data

    0x50F~513 1295~1299 Reserved 4.2.10 Input Data Area-Default CMD 3 Simple Format Data When configure HRT-711 default CMD 3 to simple format, the data of Modbus address for each HART device is shown as following table. Byte 0 Byte 1 Byte 2...
  • Page 28: Output Data Area

    Channel selection in through mode 0x76D 1901 Send data length in through mode 0x76E~7FB 1902~2043 Send data in through mode NOTE 1:When write the value greater than zero, the module will clear module request count, module HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 29: Through Mode

    Receive length in through mode and the user can get receive data from Receive data in through mode [Address:1153 ~ ] according to receive data length. [Address:1152] (If the Error count in through mode is different than the last value, it means it can not receive any data.) HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 30: Section 5- Utility

    5.1 .NET Framework Installation The Utility for HRT-711 needs .NET Framework to run. The version of .NET Framework to execute Utility has to greater than 2.0. If users do have this, please ignore this section and jump to section 5.2.
  • Page 31: Install Hrt-711 Utility

    Step 1:Download the installation file of HRT-711 Utility from the CD-ROM disk (CD:\hart\gateway\hrt-711\utilities\) or the web site (ftp://ftp.icpdas.com.tw/pub/cd/fieldbus_cd/hart/gateway/hrt-711/utilities/) Step 2:Execute the HRT-711 Utility x.x.x.x.exe (x.x.x.x is the version of the install package) file to install the Utility, and then click Next button. HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 32 Step 3:Click the Next button to continue. If you want to change the installation destination, click Browse button to select the installation path. Step 4:Choose the name and the path to install in the Start Menu, and then click Next. Step 5:Click Install to start installation HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 33 Step 6:Wait the installation finish, then check “View Patch Note.txt” if you want and click Finish to complete the installation. Step 7:Users can execute the Utility in the follow path. Windows XP Windows 7 HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 34: Introduction Of Utility

    Click Search Servers in this form to search all ICPDAS devices. The HRT-711 will list in this form after searching. If the HRT-711 does not list in this form, please check the network connection or the power of the HRT-711.
  • Page 35: Configuration Of Modbus To Hart

    After assigning parameter, user can click Exit to exit the Network Configuration form. 5.5 Configuration of Modbus to HART The HRT-711 is the Modbus/TCP to HART gateway. It not only has to configure the Ethernet but also the HART interface.
  • Page 36: Traffic Light

    Com port. 5.5.5 Tools The Utility contains many tools for configuration and debug. The following table lists all tools and its functionalities. Tool Functionality Communication Setting The Com Port setting for the PC HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 37 Translate Packed ASCII and IEEE 754 format 5.5.5.1 Communication Settings User can choose what device to configure. In this manual, please select HRT-711 in the dropdown list, and then select the Com Port number connected to HRT-711. HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 38 Right Click Generate Pop-up menu Basic Operation and Advanced Operation (1) When right clicking the item of System, it will generate a pop-up menu. The functionalities of the menu will describe below: Basic Operation  HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 39 It will show the latest HART UserCmd that has error happened. If the index user value is 255, it means no error happened command Update When click the button, it will update System Input data from the module button Advanced Operation  HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 40 And when click this button, it will update the input and output data from the module. NOTE:About the Input data area of user command, the first 2 bytes are response code1 and code2 of HART command and the left bytes are the HART command data. HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 41 (1) When right clicking the item of System, it will generate a pop-up menu. The functionalities of the menu will describe below: Edit  It is used to set the communicating parameters of HART and Modbus and described as below. HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 42 The polling interval of HART Cmd Timeout The timeout value of HART Cmd. Value If the function is enabled, the HRT-711 will execute all HART polling Cmd Auto Polling automatically. When HART comm. error happened, the HRT-711 will re-send the HART Retry Count Cmd for Retry count times.
  • Page 43 Device ID 則可忽略 (1) Disable:The HRT-711 will not execute the default HART Cmd (2) Initial:The HRT-711 will execute the default HART Cmd automatically when in Initial mode. (3) Polling:The HRT-711 will execute the default HART Cmd automatically when in Operation mode.
  • Page 44 (2) Double click the address field and it will show the Data Edit window to set the default value. When finished all configuration, click Save to Device button to apply all setting. (The module will reboot HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 45 (3) The data of Modbus AO table can be read by Modbus Function Code 3 and written by Modbus Function Code 6 or 16. NOTE:The Modbus address of the default command is fixed, so users can refer to section 4.2 to get the address. HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 46 (2) Status Update button:Refresh the status of HART Cmd (3) Record button : The HRT-711 records the latest error command and saves to Record 1~3. Users can get these records by click Record 1, Record 2 and Record 3 button.
  • Page 47 Step 1 In Send field, fill in the data“0xFF 0xFF 0xFF 0xFF 0xFF 0x02 0x80 0x00 0x00” and then click Send button to send HART Cmd. Step 2 Click Update button to show the response of HART device. HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 48 ASCII into ASCII format. IEEE754 Translate tool can convert IEEE754 into byte format. 功能 說明 It can be used to convert between Packed ASCII and ASCII format Packed ASCII Translate It can be used to convert between IEEE754 and DWORD format IEEE 754 Translate HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 49: Appendix A Hart Command

    Float Primary Variable Command 2:Read P.V. Current and Percentage of Range Request Data Bytes Response Data Bytes 2 + 8 = 10 Byte Index Format Desciption Uint8 Response Code 1 Uint8 Response Code 2 HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 50: Command 3:Read Dynamic Variables And P.v. Current

    Polling Address Command 11:Read Unique Identifier Associated with TAG Request Data Bytes Byte Index Format Desciption TAG Name Response Data Bytes 2 + 12 = 14 Byte Index Format Desciption Uint8 Response Code 1 HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 51: Command 12:Read Message

    Day of month Uint8 Month of year Uint8 Year as offset to 1900 Command 14:Read Primary Variable Sensor Information Request Data Bytes Response Data Bytes 2 + 16 = 18 Byte Index Format Desciption HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 52: Command 15:Read Primary Variable Output Information

    Response Code 1 Uint8 Response Code 2 Uint24 Final assembly number (MSB first) Command 17:Write Message Request Data Bytes Byte Index Format Desciption 0~23 PA24 Message Response Data Bytes 2 + 24 = 26 HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 53: Command 18:Write Tag, Descriptor, Date

    Format Desciption Uint24 Final assembly number (MSB first) Response Data Bytes 2 + 3 = 5 Byte Index Format Desciption Uint8 Response Code 1 Uint8 Response Code 2 Uint24 Final assembly number (MSB first) HRT-711 Users Manual (2014/1/21, Rev: 1.00)
  • Page 54: Appendix B Command Format

    Primary Variable Percentage of Range Command 3:(Read Dynamic Variables and P.V. Current) Response Data Bytes Byte Index Format Desciption Float Primary Variable Current Float Primary Variable 8~11 Float Secondary Variable 12~15 Float Tertiary Variable 16~19 Float Quaternary Variable HRT-711 Users Manual (2014/1/21, Rev: 1.00)

Table of Contents