 DIP Switches
Number Item
1
Address MSB
2
Protocol
3
Checksum
4
ZB PID
5
6
ZB Channel
7
8
9
Data Format
ICP DAS, ZT-2017 and ZT-2017C AI Series User Manual, Version 1.0.1
Copyright © 2012 by ICP DAS Co., Ltd. All Rights Reserved.
Status Description
OFF
Valid Address (Node ID) from 0x01 to 0x0F
ON
Valid Address (Node ID) from 0x10, 0x01 to 0x1F
OFF
DCON Protocol
ON
Modbus RTU Protocol
OFF
Disabled (DCON Protocol)
ON
Enabled (DCON Protocol)
OFF
ZigBee Pan ID = 0x0000
ON
ZigBee Pan ID = 0x0001
OFF
------
ON
0x08
OFF
------
ON
0x04
OFF
------
ON
0x02
OFF
------
ON
0x01
OFF
Engineering Units Format
ON
Hexadecimal Format