Table of Contents

Advertisement

6.2.13 $AA8Ci

Description
This command is used to read the type code information for a specific channel on
a specified module.
Syntax
$AA8Ci[CHECKSUM](CR)
$
Delimiter character
AA
The address of the module to be read in hexadecimal format (00 to FF)
8
The command to read the type code of the channel
Ci
Specifies which channel to access for the type code information (0-7)
Response
Valid Command
Invalid Command
!
Delimiter character to indicate a valid command
?
Delimiter character to indicate an invalid command
AA
The address of the responding module in hexadecimal format (00 to FF)
Ci
i specifies which input channel the type code information relates to.
Rrr
rr represents the type code of the specified input channel. See Section 4
for details.
There will be no response if the command syntax is incorrect, there is a
communication error, or there is no module with the specified address.
Example
Command $038C0
Response
!03C0R08
Reads the Type Code for channel 0 of module 03 and returns a response
indicating that the command was successful, with a value of 8 (-10 ~ +10V).
Command $038C9
Response
?03
Attempts to read the type code for channel 9 of module 03 and returns a
response indicating that the command was unsuccessful because the channel 9
does not exist.
ICP DAS, ZT-2017 and ZT-2017C AI Series User Manual, Version 1.0.1
Copyright © 2012 by ICP DAS Co., Ltd. All Rights Reserved.
!AACiRrr[CHECKSUM](CR)
?AA[CHECKSUM](CR)
Page 55

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zt-2017c