Setting up the ZT-2000 I/O Device

3.1 Introduction to the Configuration
Parameters
A. The "ZB PID" parameter is the group identity for a ZigBee network, and
must be the same for all devices in the same ZigBee network.
B. The "Node ID" parameter is the individual identity of the specific ZigBee
module, and must be unique for each device connected to the same
ZigBee network.
C. The "ZB Channel" parameter indicates the radio frequency channel, and
must be set to the same value as other modules on the same ZigBee
network.
ZB Channel
Frequency (MHz)
ZB channels 0x04, 0x09, 0x0E or 0x0F are recommended because they do not
overlap with the Wi-Fi frequency band.
2400
00 01 02 03
MHz
D. Protocol/Application Mode:
When implementing custom programs based on different protocols, the
following application mode(s) are recommended in order to ensure optimal
performance.
ICP DAS, ZT-2017 and ZT-2017C AI Series User Manual, Version 1.0.1
Copyright © 2012 by ICP DAS Co., Ltd. All Rights Reserved.
0x00
2405
802.11b/g
ZB Channel 1
04
05 06 07 08
0x01
......
2410
......
802.11b/g
ZB Channel 6
09
0A 0B 0C 0D
802.11b/g ZB Channel (North America)
802.15.4 ZB Channel
0x0F
2480
802.11b/g
ZB Channel 11
0E 0F