Table of Contents

Advertisement

6.2.30 @AADHCi

Description
This command is used to disable the high alarm for a specific channel of a
specified module.
Syntax
@AADHCi[CHECKSUM](CR)
@
Delimiter character
AA
The address of the module to be configured in hexadecimal format (00
to FF)
DH
The command to disable the high alarm
Ci
The channel where the alarm is to be disabled, zero based
Response
Valid Command
Invalid Command
!
Delimiter character to indicate a valid command
?
Delimiter character to indicate an invalid command
AA
The address of the responding module in hexadecimal format (00 to FF)
There will be no response if the command syntax is incorrect, there is a
communication error, or there is no module with the specified address.
Examples
Command @03DHC0
Response
!03
Disables the high alarm for channel 0 of module 03 and returns a response
indicating that the command was successful.
Command @03DI
Response
!03FEFF
Reads the status of the alarms for module 03 and returns a response indicating
that the command was successful, and that the high alarm for channel 0 is
disabled and all others are enabled.
Command @03DHC9
Response
?03
ICP DAS, ZT-2017 and ZT-2017C AI Series User Manual, Version 1.0.1
Copyright © 2012 by ICP DAS Co., Ltd. All Rights Reserved.
!AA[CHECKSUM](CR)
?AA[CHECKSUM](CR)