6.2.8

$AA2

Description
This command is used to read the configuration of a specified module.
Syntax
$AA2[CHECKSUM](CR)
$
Delimiter character
AA
The address of the module to be read in hexadecimal format (00 to FF)
2
The command to read the configuration of the module
Response
Valid Command
Invalid Command
!
Delimiter character to indicate a valid command
?
Delimiter character to indicate an invalid command
NN
The address of the module that is saved in the EEPROM in hexadecimal
format (00 to FF)
TT
00 (Reserved)
CC
0A (Reserved)
FF
The data format, checksum settings and filter settings for the module. See
Section 4 for details.
There will be no response if the command syntax is incorrect, there is a
communication error, or there is no module with the specified address.
Examples
Command $032
Response
!FF000A00
In Normal mode, reads the configuration of module 03. The response indicating
that the command was successful and shows that the address stored in the
EEPROM is 0xFF, 60 Hz rejection and engineering units format.
Command $FF2
Response
!FF000A00
In Software Configuration mode, reads the configuration of module FF. The
response indicating that the command was successful and shows that the
ICP DAS, ZT-2017 and ZT-2017C AI Series User Manual, Version 1.0.1
Copyright © 2012 by ICP DAS Co., Ltd. All Rights Reserved.
!NNTTCCFF[CHECKSUM](CR)
?AA[CHECKSUM](CR)