P5.TT
P5.TT is used to set the mode of controlling the start and stop of the inverter with FWD and REV
terminals when run command reference mode is terminal.
0: Two wire control T
T: Two wire control T
Figure6−T5 Two wire control mode T
T: Three wire control T
When one of P5.00 to P5.06 (digital terminal function XT to X7) is set to "4: Three−wire control" .
See the following figure, when K3 is ON, FWD and REV can be activated; when K3 is OFF, FWD and
REV can not be activated.
The rising edge of FWD terminal means run forward command, while the rising edge of REV terminal
means run reverse command.
3: Three wire control T
When one of P5.00 to P5.06 (digital terminal function XT to X7) is set to "4: Three−wire control" .
See the following figure, when K3 is ON, FWD and REV can be activated; when K3 is OFF, FWD and
REV can not be activated.
The rising edge of FWD terminal means run command; REV terminal in OFF status means run
forward command, REV terminal in ON status means run reverse command.
Figure6−T7 Three−wire control mode T
80
E5 Series High Performance Universal Inverter
StartTstop mode selection
Chapter 6 Parameter Descriptions
User's Manual
Figure6−T6 Two wire control mode T
FWD
REV
Inverter
Xi
COM
Figure6−T8 Three−wire control mode T
0 ~ 3(0)
K1
K2
K3