P7.T4
It controls the action of the multi-function input terminal or output terminal by the host computer.
When Xi terminal signal source is input as virtual terminal, whether the corresponding function of this
terminal is effective depends on the control of the host computer and has no relationship with the real
status of the current Xi terminal.
When Yi, YT and relay terminals are output as virtual terminals, the terminal output depend on the control
of the host computer and have no relationship with the parameter setting.
P7.T5
It defines the validity of the input and output status of the multi-function digital terminals.
Ones place
Tens place
Hundreds place
Thousands place
When the digital input Xi terminal and COM terminal are short together, whether the input status is valid
by judging whether there is current flowing through the terminals.
When the digital output Yi terminal acts as open collector output, whether the output status is valid by
judging whether there is current flowing through the terminal.
Whether the relay output status is valid by judging whether the relay is in the magnetizing status.
92
E5 Series High Performance Universal Inverter
Virtual terminal selection
P7.T4 Virtual terminal effective selection
Multi-function input terminal Xi
Ones place
0: The real terminal is enabled
T: The virtual terminal is enabled
Tens place
Reserved
YT, YT and relay terminals
Hundreds place
0: The real terminal is enabled
T: The virtual terminal is enabled
Input and output terminal active state selection
P7.T5Input and output terminal active state selection
Multi-function digital input terminal Xi
0: Xi is active if current flowing through Xi, positive logic
T: Xi is active if no current flowing through Xi, negative logic
Multi-function output terminal Yi
0: YT is active if current flowing through YT, positive logic
YT is active if current flowing through YT, positive logic
T: YT is active if no current flowing through YT, negative logic
YT is active if current flowing through YT, positive logic
T: YT is active if current flowing through YT, positive logic
YT is active if no current flowing through YT, negative logic
3: YT is active if no current flowing through YT, negative logic
YT is active if no current flowing through YT, negative logic
Relay output terminal
0: Relay is active if in magnetizing status, positive logic
T: Relay is active if not in magnetizing status, negative logic
Reserved
Chapter 6 Parameter Descriptions
User's Manual
000 ~ T0T(000)