V&T E5 Series User Manual page 101

High performance universal inverter
Table of Contents

Advertisement

TT: Zero current detection arrival
When the output current is lower than the zero current detection level, the signal is enabled. Refer to
P7.T8 for details.
T3: Stop command
When the inverter is in the stop or standby status, the signal is enabled.
T4: Run command direction instruction
This function is used to output run command direction, regardless motor rotating direction.
T5: Running status direction instruction
This function is used to output run running direction of the motor.
3T: Sleep status indication
When the inverter is in sleeping status, the signal is enabled.
TT, T6, TT, T6 ~ TT, and 33 ~ 47: Reserved
The definition table of multi-function analog output and pulse output is as follows:
Setting
Output function
Output
running
48
frequency
Output reference
49
frequency
50
Output current
5T
Motor current
5T
Output torque
53
Output voltage
54
Bus voltage
55
AIT
56
AIT
57
AI3
58
DI
59
Output power
Host computer
60
percentage
Heat-sink
6T
temperature
Output
6T
frequency T
63~7T Reserved
Note:
Output frequency indicates the inverter output frequency, Output frequency T indicates the frequency
calculate by motor speed.
88
E5 Series High Performance Universal Inverter
Definition of analog output range
Max. frequency P0.TT corresponds to
T0VTT0mA
Max. frequency P0.TT corresponds to
T0VTT0mA
Two times rated current of inverter
corresponds to T0VTT0mA
Two times rated current of motor
corresponds toT0VTT0mA
Two times rated torque of motor
corresponds to T0VTT0mA
Two times max.output voltage P0.TT
corresponds to T0VTT0mA
T000V corresponds to T0VTT0mA
T0V corresponds to T0VTT0mA
T0mA corresponds to T0VTT0mA
Same as AIT
−T0V ~ T0V corresponds to 0 ~ T0VTT0mA
Max. input pulse frequency P5.T0
corresponds to T0VTT0mA
T times rated output power of motor
corresponds to T0VTT0mA
T0000 corresponds toT0VTT0mA
0 to T00 ℃ corresponds to 0 to T0VTT0mA
Max. frequency P0.TT corresponds to
T0VTT0mA
Chapter 6 Parameter Descriptions
User's Manual
Definition of pulse output range
Max. frequency P0.TT corresponds to P7.T0
Max. frequency P0.TT corresponds to P7.T0
Two times rated current of inverter
corresponds to P7.T0
Two times rated current of motor corresponds
to P7.T0
Two times rated torque of motor corresponds
to P7.T0
Two times max. output voltage P0.TT
corresponds to P7.T0
T000V corresponds to P7.T0
T0V corresponds to P7.T0
T0mA corresponds to 50% of P7.T0
Same as AIT
−T0V ~ T0V corresponds to 0 ~ P7.T0
Max. input pulse frequency P5.T0
corresponds to P7.T0
T times rated output power of motor
corresponds to P7.T0
T0000 corresponds to P7.T0
T00 ℃ corresponds to P7.T0
Max. frequency P0.TT corresponds to
T0VTT0mA