0: Disabled
T: Enabled
After a power failure, the function supports automatic restart the unit if power on again. This function
should be used judiciously.
When automatic restart function is activated, if the inverter in running status before power off, it will
restart automatically if power on again under any run command channel, such as operation panel,
terminal or host computer.
When automatic restart function is activated, if P0.06=T and the FWD or REV terminal is enabled when
power on, the inverter will start automatically without the need for the personal to intervene. This function
should be used judiciously.
Note:
If this function does required, to ensure this function is actually valid under terminal run command
channel, please don't change the status of run command terminal after power off.
Pb.T7
Pb.T8
When start the inverter, the reference frequency is pre−set frequency and lasts pre−set frequency
operating time Pb.T8, then other frequency reference is enabled.
Pb.T9
Pb.T0
This function supports sleep function and energy saving operation. After receive a run command:
Reference frequency≥Pb.T9, start and accelerate to reference frequency
Reference frequency≤Pb.T0, decelerate to 0 Hz
Proper setting the value can avoid the start and stop frequently. The function often used for situations
such as air condition, fan and pump, convert the analog of temperature or pressure to frequency to
control automatic start and stop.
108
E5 Series High Performance Universal Inverter
Automatic restart
Automatic restart waiting time
Pre-set frequency
Pre-set frequency operating time
Wake-up frequency
Sleep frequency
Figure 6−37 Wake-up and sleep frequency operation
Chapter 6 Parameter Descriptions
User's Manual
0 ~ T(0)
0.0 ~ T0.0 s (0.5s)
0.00 ~ 300.00 Hz (0.00Hz)
0.0 ~ 3600.0 s(0.0s)
0.00 ~ 300.00 Hz(0.00Hz)
0.00 ~ 300.00 Hz(0.00Hz)