PA.T0
0: Fault is not locked.
T: Fault is locked: Allowing re-display faults that is occurred last power-off after power
RESET before start.
Note:
 Whether to output fault indication simultaneously is decided by parameter PA.TT. Refer to PA.TT
instruction.
 "-LU-" under voltage cannot be locked upon next time power on as a fault.
PA.TT
PA.TT
The function is used to automatic reset for ordinary fault. The inverter will start to run automatically again
after automatic reset interval PA.TT. If the fault still exists as the inverter starts again after automatic
reset times PA.TT, it will output fault and stop. For faults such as over-current or over-voltage occurred
occasionally, the function can be used if the equipment need to keep running without manual reset.
Note:
 For fault E.PCU, E.rEF, E.AUt, E.FAL, E.oUt, E.otT, E.otT, E.Cur, E.GdF, E.LVT, E.CPy, E.dL4, E.IoF
and E.oL3, automatic reset function can not automatic reset these faults.
 The inverter will not check fault during automatic reset interval.
104
E5 Series High Performance Universal Inverter
Fault locking function selection
Automatic reset times
Automatic reset interval
Chapter 6 Parameter Descriptions
User's Manual
0 ~ T(0)
on, fault must be
0 ~ T0(0)
T.0 ~ T0.0 s (T.0s)