The application environment (such as temperature, humidity, dust and powder, wool, smoke and
oscillation), burning and wearing of internal devices and other factors may reduces the service life. To
reduce the fault and prolong the service life, it is necessary to perform daily inspections and periodic
maintenance.
Note
Note
T. Only the professionals can dismantle and replace the components.
T. Before inspection and maintenance, please make sure that the power supply to the has been shut
down for at least ten minutes or the CHARGER indicator is OFF, otherwise, electric shock may be
happened (E5−H−4TTTG and above power class, E5−A−4TT5 and above power class has CHARGER
indicator).
3. Do not leave metal components and parts in the inner of inverter, otherwise, inverter me be damaged.

8.T Daily Inspections

The inverter should be used under the allowable conditions as recommended in this manual and its daily
inspections should be performed as the table.
Item
Environment
Inverter
Motor
E5 Series High Performance Universal Inverter

Chapter 8 Maintenance and Inspection

Inspection Contents
Temperature
Humidity
Dust, oil, water and drop Visual check
Vibration
Gas
Heat dissipation effect
Noise
Gas
Physical appearance
Heat-sink fan ventilation Visual check
Input current
Input voltage
Output current
Output voltage
Heat dissipation effect
Noise
Vibration
Chapter 8 Maintenance and Inspection
Inspection Means
Thermometer
hygrometer
Special test instrument
Special test instrument,
smell check and visual
check
Special test instrument
Listen
Smell and visual check
Visual check
Ampere-meter
Voltmeter
Ampere-meter
Voltmeter
Special test instrument
and smell
Listen
Special test instrument
User's Manual
Criteria
−T0 ~ +40ºC
De-rated at 40 to 50ºC, and the rated
output current shall be decreased by
T% for every temperature rise of TºC.
5 ~ 95%, no condensing
No dust, no oil, no water and no drop
T
3.5mTs
, T~ 9Hz
T
T0mTs
,9~ T00Hz
T
T5mTs
,T00~ 500Hz
No abnormal smell and no smoke
Exhaust normal
There is no abnormal noise
There are no abnormal smell and
smoke
The physical appearance is kept
intact
There are no fouling and wool that
block the air duct
In the allowable operating range, refer
to the nameplate
In the allowable operating range, refer
to the nameplate
In the rated value range. It can be
overloaded for a short while
In the rated value range
There are no over temperature and
burning smell
There is no abnormal noise
There is no abnormal oscillation