Table 62 Apl Led; Table 63 Status Of The Ethernet/Ip Module - WAGO 765-1503/100-000 Product Manual

I/o system field. 16-channel digital output; ethernet/ip; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

765-1503/100-000
LED
APL
EtherNet/IP Adapter Status
The MS and NS LEDs indicate the status of the EtherNet/IP module.
The LNK and ACT LEDs indicate the Ethernet status.
LED
MS
(module status)
NS
(Network status)
Product manual | Version: 2.0.0
16DO FLD EI DC 24V 2.0A
Color
State
Duo LED, red/green/yellow (yellow = simultaneously red and green)
Off
Off
Color
State
Duo LED, red/green
Green
On
Green
Flashing (1 Hz)
Green/red/green
Rapid flashing:
green/red/green
Red/green/off
Flashing sequence:
red/green/off
Red
Flashing (1 Hz)
Red
On
Off
Off
Duo LED, red/green
Green
On
Green
Flashing (1 Hz)
Diagnostics
Table 62: APL LED
Description
LED without function
Table 63: Status of the EtherNet/IP module
Description
Module in operation: The module is in op-
eration and working correctly.
Standby: The module has not been config-
ured.
Self test: The module runs through a self
test after it is switched on. The following se-
quence occurs during the self test:
NS LED off
MS LED lights up green for about
250 ms, turns red for about 250 ms and
then lights up green again (and contin-
ues to do so until the test is completed).
NS LED lights up green for about
250 ms, turns red for about 250 ms and
then goes out (and remains off until the
test is completed).
Flashing sequence: The flashing se-
quence identifies the adapter visually. The
scanner can start the flashing sequence in
identity object 1 of the adapter. The MS
LED and NS LED go through the flashing
sequence simultaneously.
Serious recoverable error: The module
has identified an error that is serious but
can be fixed – for example, an incorrect or
inconsistent configuration may be classified
as a serious recoverable error.
Serious unrecoverable error: The module
has identified an error that is serious and
cannot be fixed.
Switched off: The module is switched off.
Connected: An IP address is configured, at
least one CIP connection (of any transport
class) has been established, and, for an
Exclusive Owner connection, the time limit
has not been exceeded.
No connection: An IP address has been
configured, but no CIP connections have
been established, and, for an Exclusive
Owner connection, the time limit has not
been exceeded.
97

Advertisement

Table of Contents
loading

Table of Contents