Commissioning
4. In the OPC UA client, drag the "AssignedForceID" node into the Data Access View
window so that the AssignedForceID is read regularly
ð Regular reading of the AssignedForceID triggers the watchdog timer and keeps
10.3.3.1.10.4 Forcing Digital Outputs
The OutputPin2 method sets the output value of pin 2 of one or more ports. The Output-
Pin4 method sets the output value of pin 4 of one or more ports.
Requirements
• You must have an OPC UA client.
• You must know the username and password, and this user must have permission to
execute methods.
• You must have already established a connection to the I/O module.
• The Force function must be enabled, i.e. you must know the Force ID.
• The pin must be configured as a digital output.
Step-by-Step Instructions
1. In the Address Space window, open the context menu: Root > Objects > De-
viceSet > [device name] > Forcing > OutputPin4
2. In the context menu, select Call.
ð The Call OutputPin4 on Forcing window appears.
3. Enter the Force ID, the Force Mask and the Force Data (the input arguments are
described below, including an example).
92
Product manual | Version: 2.0.0
16DO FLD EI DC 24V 2.0A
the Force function enabled.
765-1503/100-000
Figure 34: GetForcingID Method: Unsuccessful