Commissioning
4. In the Configuration Name field, enter a name for your configuration, e.g. "Test."
5. Select the Advanced tab.
6. In the Server Information section of the Advanced tab, enter the following informa-
tion in the Endpoint URL field: opc.tcp://<IP address>:4840. For <IP ad-
dress>, use the module's IP address.
7. In the Authentication Settings section, select the Username/Password option for
write access to the module or Anonymous for read access.
8. If you selected the Username/Password option, enter your username and, if appli-
cable, password there.
86
Product manual | Version: 2.0.0
16DO FLD EI DC 24V 2.0A
765-1503/100-000
Figure 27: Add Server Dialog – Advanced Tab