Goodrive350A series high-performance multifunction VFD
Function
Name
code
Corresponding
P05.30
setting of AI2 lower
limit
P05.31
AI2 middle value 1
Corresponding
P05.32
setting of AI2 middle
value 1
P05.33
AI2 middle value 2
Corresponding
P05.34
setting of AI2 middle
value 2
P05.35
AI2 upper limit
Corresponding
P05.36
setting of AI2 upper
limit
P05.37
AI2 input filter time
HDIA high-speed
P05.38
pulse input function
selection
Description
application section for details.
The following figure illustrates the cases of
several settings:
Corresponding setting
100%
-10V
0
AI1
AI2
-100%
Input filter time: to adjust the sensitivity of
analog input. Increasing the value properly
can enhance analog input anti-interference
but may reduce the sensitivity of analog input.
Note: AI1 supports the 0–10V/0–20mA input.
When AI1 selects the 0–20mA input, the
corresponding voltage of 20mA is 10V. AI2
supports the -10–+10V input.
Setting range of P05.24: 0.00V–P05.26
Setting range of P05.25: -300.0%–300.0%
Setting range of P05.26: P05.24–10.00V
Setting range of P05.27: -300.0%–300.0%
Setting range of P05.28: 0.000s–10.000s
Setting range of P05.29: -10.00V–P05.31
Setting range of P05.30: -300.0%–300.0%
Setting range of P05.31: P05.29–P05.33
Setting range of P05.32: -300.0%–300.0%
Setting range of P05.33: P05.31–P05.35
Setting range of P05.34: -300.0%–300.0%
Setting range of P05.35: P05.33–10.00V
Setting range of P05.36: -300.0%–300.0%
Setting range of P05.37: 0.000s–10.000s
0: Input set through frequency
1: Reserved
2: Input set through encoder, used together
with HDIB
-177-
AI
10V
20mA
Function parameter list
Default
Modify
○
-100.0%
○
0.00V
○
0.0%
○
0.00V
○
0.0%
○
10.00V
○
100.0%
○
0.030s
◎
0
Need help?
Do you have a question about the Goodrive350A Series and is the answer not in the manual?