INVT Goodrive350A Series Operation Manual page 155

Table of Contents

Advertisement

Goodrive350A series high-performance multifunction VFD
Function
Name
code
short-circuit braking
for start
Hold time of
P01.31
short-circuit braking
for stop
Pre-exciting time of
P01.32
Starting frequency
P01.33
of braking for
jogging to stop
P01.34 Delay to enter sleep 0–3600.0s
P02—Parameters of motor 1
Function
Name
code
P02.00
Type of motor 1
Rated power of AM
P02.01
Rated frequency of
P02.02
AM 1
Rated speed of AM
P02.03
Rated voltage of AM
P02.04
Rated current of AM
P02.05
Stator resistance of
P02.06
AM 1
Rotor resistance of
P02.07
AM 1
Leakage inductance
P02.08
of AM 1
During stop, if the running frequency of VFD
is lower than the starting frequency P01.09 of
brake for stop, set P01.31 to a non-zero value
to enter short-circuit braking for stop, and
then carry out DC braking in the time set by
P01.12. (Refer to the descriptions for
P01.09–P01.12.)
Setting range of P01.29: 0.0–100.0% (VFD)
Setting range of P01.30: 0.0–50.00s
Setting range of P01.31: 0.0–50.00s
0–10.000s
jog
0.00Hz–P00.03
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
0.1–3000.0kW
1
0.01Hz–P00.03 (Max. output frequency)
1–60000rpm
1
0–1200V
1
0.8–6000.0A
1
0.001–65.535Ω
0.001–65.535Ω
0.1–6553.5mH
Description
Description
-150-
Function parameter list
Default
Modify
0.00s
0.000s
0.00Hz
0.0s
Default
Modify
0
Model
depended
50.00Hz
Model
depended
Model
depended
Model
depended
Model
depended
Model
depended
Model
depended