Connecting The Signal Cables - Endress+Hauser HART Proline Promass E 200 Operating Instructions Manual

Coriolis mass flow measuring system
Hide thumbs Also See for HART Proline Promass E 200:
Table of Contents

Advertisement

Proline Promass E 200 HART
Endress+Hauser
7.2.1

Connecting the signal cables

1. Loosen the securing clamp of the connection compartment cover.
2. Unscrew the connection compartment cover.
3. Push the cable through the cable entry. To ensure tight sealing, do not remove the sealing ring
from the cable entry.
4. Strip the cable and the cable ends. For stranded cables, also attach wire end ferrules.
5.
å 6
Example for terminal assignment (on the nameplate of the I/O electronics module)
Connect the cable in accordance with the terminal assignment. For shielded cable
(recommended for HART communication): When connecting the cable shielding to the ground
terminal, observe the grounding concept of the facility. Rigid conductors or flexible conductors
with wire end ferrule can be inserted directly into the terminal without pressing on the wire
release.
6. Firmly tighten the cable glands.
7. NOTICE! Housing degree of protection voided due to insufficient sealing of the housing. Screw
in the thread without using lubricant. The cover threads are coated with a dry lubricant.
Screw the connection compartment cover closed and tighten the securing clamp.
3 mm
20 mm
mm (in)
2-wire / Flow
4-20 mA
4-20 mA
HART
[04/05]
3 4
Electrical connection
10 (0.4)
Spare part
71108602
1 2
A0013836
A0014089
25