Commissioning
64
10.4.6

Configuring the partial filled pipe detection

The Partial filled pipe detection wizard guides you systematically through all parameters that
have to be set for configuring the monitoring of the pipe filling.
Navigation path
"Setup" menu ® Partial filled pipe detection
Sequence of the wizard
Off
å 16
"Partial filled pipe detection" wizard in the "Setup" menu
Parameter overview with brief description
Parameters
Assign process variable
Low value partial filled pipe
detection
High value partial filled pipe
detection
Response time part. filled pipe
detect.
Assign process
variable
Density
Description
Select a process variable to detect
empty or partially filled pipes.
Enter a lower limit value to
activate detection of an empty or
partially filled pipe.
Enter an upper limit value to
activate detection of an empty or
partially filled pipe.
Enter the time interval until the
diagnostic message
S862
Partly filled pipe detection is
displayed for an empty or partially
filled pipe.
Proline Promass E 200 HART
Reference
density
Low value
partial filled
pipe detection
High value
partial filled
pipe detection
Response time
part. filled
pipe detect.
End of wizard
Selection/
User entry
• Off
• Density
• Reference density
Max. 15-digit, positive floating-
point number
Max. 15-digit, positive floating-
point number
0 to 100 s
Endress+Hauser
A0013801-EN
Factory
setting
Density
Country-
dependent:
• 0.2 kg/l
• 12.5 lb/cf
Country-
dependent:
• 6 kg/l
• 374.6 lb/cf
1 s