Density measurement with Density Computer FML621
1
Liquiphant Density → Pulse output
2
Temperature sensor, e.g. 4 to 20 mA output
3
Pressure transmitter 4 to 20 mA output required for changes in pressure >6 bar
4
Liquiphant Density Computer FML621 with display and operating unit
5
PLC
The measurement can be affected by:
• air bubbles at the sensor
• unit not fully covered by the medium
• solid media buildup on the sensor
• high flow velocity in pipes
• severe turbulence in the pipe due to inlet and outlet runs that are too short
• corrosion of the fork
• non-Newtonian (not purely viscous) behavior of media
6.3.2

Connecting the cables

Required tools
• Flat-blade screwdriver (0.6 mm x 3.5 mm) for terminals
• Suitable tool with width across flats AF24/25 (8 Nm (5.9 lbf ft)) for M20 cable gland
-
1
1
2
3
1
2
3
Electrical connection
.
4
5
4
5