Parameter overview with brief description
Parameters
Prerequisite
Assign simulation
-
process variable
Value process variable One of the following
options is selected in
the Assign process
variable parameter:
• Mass flow
• Volume flow
• Corrected volume
flow
• Density
• Reference density
• Temperature
Simulation current
-
output 1-2
Value current output
The On option is
1-2
selected in the
Simulation current
output 1-2 parameter
Simulation device
-
alarm
10.8

Protecting settings from unauthorized access

The following options exist for protecting the configuration of the measuring device from
unintentional modification after commissioning:
• Write protection via access code (® ä 73)
• Write protection via lock switch (® ä 74)
• Write protection via keypad lock (® ä 42)
10.8.1

Write protection via access code

Using the customer-specific access code, the parameters for the measuring device configuration are
write-protected and their values can no longer be changed via local operation.
Define access code
1. Navigating to the "Define access code" parameter: Setup ® Advanced setup ® Def. access
code
2. Define a max. 4-digit numeric code as an access code.
à The -symbol appears in front of all write-protected parameters.
Description
Selection/
User entry
Select a process
• Off
variable for the
• Mass flow
simulation process that
• Volume flow
is activated.
• Corrected volume
flow
• Density
• Reference density
• Temperature
Enter the simulation
Depends on the
value for the selected
process variable
process variable.
selected
Switch simulation of
• On
the current output on
• Off
and off.
Enter the current value
3.6 to 22.5 mA
for simulation.
Switch the device
• On
alarm on and off.
• Off
Commissioning
Factory setting
Off
-
Off
Current value
currently measured
Off
73