12.2

Diagnostic information on local display

12.2.1

Diagnostic message

Faults detected by the self-monitoring system of the measuring device are displayed as a diagnostic
message in alternation with the measured value display.
Measured value display in alarm condition
X X X X X X X
X
X
20.50
2
1
Status signal
2
Symbol for event level
3
Symbol for event level with diagnostic event
4
Event text
5
Operating elements
Status signals
"Failure"
A device error is present. The measured value is no longer valid.
A0013956
"Function check"
The device is in service mode (e.g. during a simulation).
A0013959
"Out of specification"
The device is operated:
• Outside of its technical specifications (e.g. during startup or a cleaning)
• Outside of the configuration carried out by the user (e.g. maximum flow in parameter 20 mA
A0013958
value)
"Maintenance required"
Maintenance is required. The measured value is still valid.
A0013957
The status signals are categorized according to VDI/VDE 2650 and NAMUR Recommendation
NE 107: F = Failure, M = Maintenance Required, C = Function Check, S = Out of Specification
Symbols for event level
"Alarm"
The measurement is interrupted. The signal outputs take on the defined alarm condition. A
diagnostic message is generated.
A0013961
"Warning"
The device continues to measure. The signal outputs are not affected. A diagnostic message is
generated.
A0013962
2
1
S
X X X X X X X
X
S441
Curr. output 1
mA
Diagnostics and troubleshooting
Diagnostic message
S
X
3
4
Menu
i
5
A0013939-EN