Deutschmann Automation GmbH & Co. KG
16.1.1 Interface data
The table below lists the technical data of the interfaces and ports on the device. The data has
been taken from the corresponding Standards.
Interface designation
No. Physical interface
1
Standard
2
Transmission mode
3
Transmission method
4
Number of users : - Transmitters
5
Cable length: - Maximum
- Baud rate-dependent
6
Bus topology
7
Data rate: - Maximum
- Standard values
8
Transmitter: - Load
- Maximum voltage
- Signal, unloaded
- Signal, loaded
9
Receiver:
- Input resistance
- Max. input signal
- Sensitivity
10
Transmit range (SPACE):
11
Transmit pause (MARK):
Table: Technical data of the interfaces and ports on the module
25.9.20
Fieldbus-Gateway UNIGATE
CANopen
RS485
®
CiA
Symmetrical
asynchronous
serial
half-duplex
Difference signal
Master / slave
32
- Receivers
32
1300 m
50 kBd 1300 m
100 kBd 640 m
200 kBd 310 m
500 kBd 112 m
1 MBd 40 m
Line
1Mbit/s
125 kB
250 kB
500 kB
1 MB
54
- 7 V ... 12 V
5 V
1.5 V
12
- 7 V ... 12 V
0.2 V
- Voltage level
- 0.5 ... + 0.05 V
- Logic level
0
- Voltage level
+ 1.5 ... +3 V
- Logic level
1
®
RS232-C
®
RS232-C
DIN 66020
DS 102
Asymmetrical
asynchronous
serial
full duplex
Level
Master / slave Master / slave
1
1
15 m
no
Point-to-point
120 kBit/s
2.4 k/B
4.8 k/B
9.6 kBit/s
19.2 kBit/s
38.4 kBit/s
3 ... 7 k
25 V
15 V
5 V
3 ... 7
15 V
3 V
+ 3 ... + 15 V
0
- 3 ... –15 V
1
CX C4Map - DeviceNet V. 1.0
Technical data
DeviceNet
®
CiA
DS 102
Symmetrical
asynchronous
serial
half-duplex
Difference signal
32
32
500 m
125 kB 500 m
250 kB 250 m
500 kB 100 m
Line
500 kBit/s
125 kB
250 kB
500 kB
54
- 7 V ... 12 V
5 V
1.5 V
12
- 7 V ... 12 V
0.2 V
- 0.5 ... + 0.05 V
0
+ 1.5 ... +3 V
1
45
Need help?
Do you have a question about the UNIGATE CX-CANopen - DeviceNet and is the answer not in the manual?