11 Installation guidelines

11.1 Installation of the module

The module with the dimensions 23 x 117 x 111 mm resp. 23 x 117 x 117 mm with Option I/O8 (W
x D x H) has been developed for switch cabinet use (IP 20) and can thus be mounted only on a
standard mounting channel (deep DIN-rail to EN 50022).

11.1.1 Mounting

Engage the module from the top in the top-hat rail and swivel it down so that the module
engages in position.
Other modules may be rowed up to the left and right of the module.
There must be at least 5 cm clearance for heat dissipation above and below the module.
The standard mounting channel must be connected to the equipotential bonding strip of the
switch cabinet. The connection wire must feature a cross-section of at least 10 mm².

11.1.2 Removal

First disconnect the power supply and signal lines.
Then push the module up and swivel it out of the top-hat rail.
Vertical installation
The standard mounting channel may also be mounted vertically so that the module is mounted
turned through 90°.
11.2

Wiring

11.2.1 Connection systems - DeviceNet

The following connection systems must resp. may be used when wiring the module:
Standard screw-type/plug connection (power supply + Debug)
Standard screw-type/plug connection (DeviceNet)
a) In the case of standard screw-type terminals, one lead can be clamped per connection point. It
is best to then use a screwdriver with a blade width of 3.5 mm to firmly tighten the screw.
Permitted cross-sections of the line:
Flexible line with wire-end ferrule:
Solid conductor:
Tightening torque:
b) The plug-in connection terminal strip is a combination of standard screw-type terminal and
plug connector. The plug connection section is coded and can thus not be plugged on the
wrong way round.
c) The 9-pin D-SUB plug connector is secured with two screws with "4-40-UNC" thread. It is best
to use a screwdriver with a blade width of 3.5 mm to screw the screw tight.
Tightening torque: 0.2... 0.4 Nm

11.2.2 Connection systems - CANopen

The following connection systems must resp. may be used when wiring the module:
Standard screw-type/plug connection (power supply + Debug)
25.9.20
Fieldbus-Gateway UNIGATE
1 x 0.25 ... 1.5 mm²
1 x 0.25 ... 1.5 mm²
0.5 ... 0.8 Nm
®