Electrical connection
6.3.3.

Fieldbus cables: connect

6.3.3.1. Fieldbus connection for line topology

Information
Information
30
SQEx 05.2
SQEx 14.2/SQREx 05.2
Figure 23: Line topology
Channel 1: Further fieldbus devices follow
Channel 2 (redundancy only): further fieldbus devices follow
Last fieldbus device
n 1
Fieldbus cable from previous device (input)
n+1
Fieldbus cable to next device (output)
Connection at terminal carrier for loop topology
For flexible cables, the fieldbus connection can be made via spring clamp terminals
directly at the terminal carrier. For solid cables (single or multiple strands), additional
support terminals must be used. Refer to <Connection with support terminals> section
For two flexible wires per terminal, a joint wire end sleeve must be used (twin wire
end sleeve).
Figure 24: Terminal assignment at terminal carrier: Channel 1 (1A/1B)
Figure 25: Terminal assignment at terminal carrier: Channel 2 (2A/2B)
[XK] Terminal assignment according to wiring diagram (customer connection):
□ ▣
Channel 1 □ or channel 2 ▣ if further fieldbus devices follow
If the actuator is the last fieldbus device:
Channel 1: Link terminals 31/33 and 32/34
Channel 2: Link terminals 35/37 and 36/38
Always link A connections to green wire and B connections to red wire.