Fieldbus Cables: Connect; 6.3.3.1. Fieldbus Connection For Line Topology - AUMA SAEx 07.2 Manual

Multi-turn actuators
Hide thumbs Also See for SAEx 07.2:
Table of Contents

Advertisement

SAEx 07.2
SAEx 16.2/SAREx 07.2
ACExC 01.2 Intrusive Modbus RTU
6.3.3.

Fieldbus cables: connect

6.3.3.1. Fieldbus connection for line topology

Information
SAREx 16.2 Control unit - electromechanical
Figure 28: Line topology
Channel 1: Further fieldbus devices follow
Channel 2 (redundancy only): further fieldbus devices follow
Last fieldbus device
n 1
Fieldbus cable from previous device (input)
n+1
Fieldbus cable to next device (output)
Connection at terminal carrier for loop topology
For flexible cables, the fieldbus connection can be made via spring clamp terminals
directly at the terminal carrier. For solid cables (single or multiple strands), additional
support terminals must be used. Refer to <Connection with support terminals> section
For two flexible wires per terminal, a joint wire end sleeve must be used (twin wire
end sleeve).
Figure 29: Terminal assignment at terminal carrier: Channel 1 (1A/1B)
Figure 30: Terminal assignment at terminal carrier: Channel 2 (2A/2B)
[XK] Terminal assignment according to wiring diagram (customer connection):
□ ▣
Channel 1 □ or channel 2 ▣ if further fieldbus devices follow
If the actuator is the last fieldbus device:
Channel 1: Link terminals 31/33 and 32/34
Channel 2: Link terminals 35/37 and 36/38
Electrical connection
33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents