Figure 25: Dialog Window Dtm Parameters - WAGO 750-482/000-001 Manual

2ai 4-20ma hart namur ne43, 2-channel analog input, 4 ma … 20 ma hart, namur ne43
Table of Contents

Advertisement

WAGO I/O System 750
750-482/000-001 2AI 4-20mA HART NAMUR NE43

Figure 25: Dialog Window DTM Parameters

16.
Select the desired module from the left side of the tree structure; the
displayed module number corresponds to the slot in the structure – module
01 is the bus coupler.
The right side contains the parameterization dialog for this module.
17.
Set the desired parameter for each channel separately, such as
When the simulation is activated, the selected simulation value is output as
a process value. When selecting an overflow or underflow, the overflow or
underflow is overlaid (last 2 bits), as output in the status byte.
the analog Filter time for the input channel (10 ms ... 640 ms),
the Simulation mode activation, and
the Simulation value setting with the Over range or Under range
selection.
Commissioning
73
Manual
Version 1.0.2