Process Image - WAGO 750-482/000-001 Manual

2ai 4-20ma hart namur ne43, 2-channel analog input, 4 ma … 20 ma hart, namur ne43
Table of Contents

Advertisement

WAGO I/O System 750
750-482/000-001 2AI 4-20mA HART NAMUR NE43
4

Process Image

Mapping of process data in the process image of fieldbus systems
The representation of the I/O modules' process data in the process image
depends on the fieldbus coupler/controller used. Please take this information as
well as the particular design of the respective control/status bytes from the
section "Fieldbus Specific Design of the Process Data" included in the description
concerning the process image of the fieldbus coupler/controller used.
Evaluation of Status Byte
Some fieldbus systems can process status information of process value by
means of a status byte.
This status byte can be displayed via the commissioning tool WAGO-I/O-
CHECK.
However, processing via the fieldbus coupler/controller is optional, which means
that accessing or parsing the status information depends on the fieldbus system.
The HART I/O module provides the fieldbus coupler/controller with a different
amount of process data depending on the operating mode set.
For pure 3.6 mA ... 21 mA analog values the HART module transmits 16-bit
measured values and optionally 8 status bits on each channel.
The digitalized measured value is transmitted to the process image of the
coupler/controller in a data word (16 bits) as an input byte 0 (low) and input byte
1 (high).
This value is mapped with a resolution of 13 bits on Bit B2 ... B14.
Status information, which can be evaluated in the event of a fault, is contained in
the two least significant bits (B0 and B1). If the measurement is above the
measuring range, Bit B0 is set = 1, and if the measurement is below the
measuring range or if a wire breaks, Bit B0 and B1 are set = 1.
The input voltage range for the measured values of 3.6 mA to 21 mA is scaled to
the numerical range from 0xFCFF to 0x7FFD.
Process Image
29
Manual
Version 1.0.2

Advertisement

Table of Contents
loading

Table of Contents