26
Device Description
3.6.6
Climatic Environmental Conditions
Table 16: Technical Data – Climatic Environmental Conditions
Surrounding air temperature, operation 0 °C ... 55 °C
Surrounding air temperature, storage
Operating altitude
Relative humidity
Pollution degree
Protection type
Resistance to harmful substances
Maximum pollutant concentration at
relative humidity < 75 %
Special conditions
Manual
Version 1.0.2
750-482/000-001 2AI 4-20mA HART NAMUR NE43
−25 °C ... +85 °C
0 ... 2000 m
Max. 5 % ... 95 % without condensation
2
IP20
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
SO
≤ 25 ppm
2
H
S ≤ 10 ppm
2
•
Ensure that additional measures for
components are taken, which are
used in an environment involving:
– dust, caustic vapors or gases
– ionizing radiation
•
Ensure that the permissible
temperature range of the connecting
cable is correct dimensioned
depending on the installation
position and current intensity,
because the clamping point
temperature at 10 A can be up to
25 °C above the expected
surrounding air temperature.
WAGO I/O System 750