Checking The Status Of A Pci Expansion Unit - Fujitsu M10-4 Service Manual

Hide thumbs Also See for M10-4:
Table of Contents

Advertisement

Table 3-1     Status of components (continue d)
Display
Deconfigured
Maintenance
3.3.4

Checking the status of a PCI expansion unit

If a PCI expansion unit is connected, execute the ioxadm command from the XSCF
shell to check the status of the PCI expansion unit.
ioxadm command
Execute the ioxadm command to check the environmental conditions (temperature,
voltage, etc.) or LED indications for the PCI expansion unit.
1.
Log in to the XSCF shell.
2.
Execute the ioxadm command to check the environmental conditions of the
specified PCI expansion unit.
To specify a PCI expansion unit, enter the serial number of the PCI expansion
unit after determining it by executing the ioxadm list command.
The following example shows the environmental conditions for the PCIBOX#2008
"2008" are the last four digits of the serial number of the PCI expansion unit.
XSCF>   ioxadm env -te PCIBOX#2008
Location                                           Sensor                           Value   Resolution   Units
PCIBOX#2008                                     AIRFLOW                     180.000             0.000   CHM
PCIBOX#2008                                     P_CONSUMPTION           68.000             0.000   W
PCIBOX#2008/PSU#0                         FAN                           3936.000             0.000   RPM
PCIBOX#2008/PSU#1                         FAN                           3584.000             0.000   RPM
PCIBOX#2008/FAN#0                         FAN                           3374.000             0.000   RPM
PCIBOX#2008/FAN#1                         FAN                           3374.000             0.000   RPM
PCIBOX#2008/FAN#2                         FAN                           3374.000             0.000   RPM
PCIBOX#2008/IOBT                           T_INTAKE                     26.000             0.000   C
PCIBOX#2008/IOBT                           T_PART_NO0                 31.500             0.000   C
PCIBOX#2008/IOBT                           T_PART_NO1                 30.750             0.000   C
PCIBOX#2008/IOBT                           T_PART_NO2                 31.500             0.000   C
PCIBOX#2008/IOBT                           V_12_0V                       12.069             0.000   V
PCIBOX#2008/IOBT                           V_3_3_NO0                     3.293             0.000   V
PCIBOX#2008/IOBT                           V_3_3_NO1                     3.295             0.000   V
PCIBOX#2008/IOBT                           V_3_3_NO2                     3.291             0.000   V
PCIBOX#2008/IOBT                           V_3_3_NO3                     3.300             0.000   V
PCIBOX#2008/IOBT                           V_1_8V                           1.804             0.000   V
PCIBOX#2008/IOBT                           V_0_9V                           0.900             0.000   V
Description
Due to the failure or degradation of another unit, the target unit and
components of its underlying layer has been degraded, though there
is no problem in them.
Maintenance is being performed. The replacefru, addfru, or initbb
command is being executed.
Chapter 3 Troubleshooting
37