5.3.1.

Terminal compartment: open

SAREx 16.2
Figure 21: Open terminal compartment
[1]
Cover
[2]
Screws for cover
[3]
O-ring
[4]
Blanking plugs
[5]
Cable gland (example)
[6]
Flameproof frame
Hazardous voltage!
Risk of electric shock.
Disconnect device from the mains before opening.
Flameproof enclosure, danger of explosion!
Risk of death or serious injury.
Before opening, ensure that there is no explosive gas and no voltage.
1.
Loosen screws [2] and remove cover [1].
2.
Insert cable glands suitable for connecting cables.
Information: When selecting cable glands observe type of protection (with Ex d
approval) and type of protection NEMA... (refer to name plate).
The type of protection stated on the name tag, NEMA... , is only ensured if
suitable cable glands are used.
Figure 22: Name tag, example with enclosure protection NEMA
3.
Seal cable entries unused cable entries with approved plugs suitable for the
required protection type.
Electrical connection