Ewg 01.1 Electronic Position Transmitter - AUMA SAEx 07.2 Manual

Multi-turn actuators
Hide thumbs Also See for SAEx 07.2:
Table of Contents

Advertisement

Commissioning (basic settings)
9.7.

EWG 01.1 electronic position transmitter

Technical data
Setting components
42
2.
Operate actuator using push buttons OPEN - STOP - CLOSE.
The limit switches are set correctly if (default indication):
-
the green indication light is illuminated in end position CLOSED
-
the red indication light is illuminated in end position OPEN
-
the indication lights go out after travelling into the opposite direction.
The limit switches is set incorrectly if:
-
the actuator comes to a standstill before reaching the end position
-
the yellow indication light is illuminated (torque fault).
3.
If the end position setting is incorrect: Reset limit switches.
4.
If the end position setting is correct and no options (e.g. potentiometer, position
transmitter) are available: Close switch compartment.
Option
EWG 01.1 electronic position transmitter signals the remote position or the valve
position. On the basis of the actual valve position sensed by hall sensor, a current
signal between 0
20 mA or 4
Table 12: EWG 01.1
Data
Output current I
a
1)
Power supply U
V
Max. current consumption
Max. load R
B
Impact of power supply
Load influence
Temperature impact
2)
Ambient temperature
1)
Power supply possible via: AC, AM controls or external power supply
2)
Depending on temperature range of the actuator: Refer to name tag
The EWG is housed in the actuator switch compartment. The switch compartment
must be opened to perform any settings. Refer to <Switch compartment: open>.
All settings are made via the two push buttons [S1] and [S2].
Figure 38: View on control unit when switch compartment is open
[S1]
Push button: Set 0/4 mA
[S2]
Push button: Set 20 mA
LED Optical aid for setting
[1]
Measuring point (+) 0/4
[2]
Measuring point ( ) 0/4
The output current (measuring range 0 20 mA) can be checked at measuring points
[1] and [2].
SAEx 07.2
SAEx 16.2 / SAREx 07.2
20 mA is generated.
3-wire and 4-wire systems
0
20 mA, 4
20 mA
24 V DC (18
32 V)
LED off = 26 mA, LED on = 27 mA
600 Ω
< 0.1 ‰/K
76 °F to 176 °F ( 60 °C to +80 °C)
20 mA
20 mA
SAREx 16.2
AUMA MATIC AMExC 01.1
2-wire system
4
20 mA
24 V DC (18
32 V)
20 mA
(U
12 V)/20 mA
V
0.1 %
0.1 %