SAEx 07.2
SAEx 16.2 / SAREx 07.2
AUMA MATIC AMExC 01.1
5.2.1.
Terminal compartment: open
SAREx 16.2
Figure 16: Terminal compartment: open
[1]
Cover
[2]
Screws for cover
[3]
O-ring
[4]
Screws for socket carrier
[5]
Socket carrier
[6]
Cable entry
[7]
Blanking plugs
[8]
Cable gland (not included in delivery)
Hazardous voltage!
Risk of electric shock.
Disconnect device from the mains before opening.
Flameproof enclosure, danger of explosion!
Risk of death or serious injury.
Before opening, ensure that there is no explosive gas and no voltage.
1.
Loosen screws [2] and remove cover [1].
2.
Loosen screws [4] and remove socket carrier [5] from cover [1].
3.
Insert cable glands suitable for connecting cables.
Information: When selecting cable glands observe type of protection (with Ex d
approval) and type of protection NEMA... (refer to name tag).
The type of protection stated on the name tag, NEMA... , is only ensured if
suitable cable glands are used.
Figure 17: Name tag, example with enclosure protection NEMA
4.
Seal unused cable entries with approved plugs suitable for the required protec-
tion type.
Electrical connection
23