Parking Frame - AUMA SAEx 07.2 Manual

Multi-turn actuators
Hide thumbs Also See for SAEx 07.2:
Table of Contents

Advertisement

Electrical connection
Design
Observe prior to connec-
tion
5.4.2.

Parking frame

Application
30
Figure 25: Design principle with wall bracket
[1]
Wall bracket
[2]
Connecting cables
[3]
Electrical connection of wall bracket (XM)
[4]
Electrical connection of actuator (XA)
[5]
Electrical connection of controls (XK) - customer plug
Permissible length of connecting cables: max. 100 m.
If the actuator is equipped with a position transmitter (EWG/RWG): Connecting
cables must be available as shielded version.
Versions with potentiometer in the actuator are not suitable.
We recommend using an AUMA cable set "LSW".
If the AUMA cable set is not used: Use suitable flexible and screened connecting
cables.
When using connecting cables, e.g. of the heater or switch, requiring direct
wiring from the actuator to the XK customer plug (XA-XM-XK, refer to wiring
diagram), these connecting cables must be subject to an insulation test in
compliance with EN 50178. Connecting cables of position transmitters (EWG,
RWG, IWG, potentiometer) do not belong to this group.They may not be subject
to an insulation test.
Option
Parking frame for safe storage of a disconnected plug or cover.
For protection against touching the bare contacts and against environmental
influences.
Explosion hazard!
Risk of death or serious injury.
Prior to opening the device (removing the plug) ensure that the device is free
of gas and voltage!
Do NOT switch on voltage in potentially explosive atmospheres.
SAEx 07.2
SAEx 16.2 / SAREx 07.2
SAREx 16.2
AUMA MATIC AMExC 01.1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sarex 07.2Saex 16.2Sarex 16.2

Table of Contents