9.6.2.

Limit switches: check

SAREx 16.2
4.
With mechanical position indication:
Observe direction of rotation.
The direction of rotation is correct if the actuator moves in direction
CLOSE and:
-
For position indication with symbols OPEN/CLOSED = indicator disc turns
counterclockwise.
Figure 36: Position indication with symbols OPEN/CLOSED
5.
Without mechanical position indication:
Unscrew threaded plug [1] and seal [2] or protective cap for stem protection
tube [4] and observe direction of rotation at hollow shaft [3] or the stem
[5].
The direction of rotation is correct if the actuator moves in direction CLOSE
in clockwise direction, or the stem moves downward.
Figure 37: Hollow shaft/stem movement for clockwise closing
[1]
Threaded plug
[2]
Seal
[3]
Hollow shaft
[4]
Protective cap for stem protection tube
[5]
Stem
[6]
Stem protection tube
1.
Set selector switch to position Local control (LOCAL).
Commissioning (basic settings)
41