Commissioning (basic settings)
9.5.2.

Running direction OPEN (white section): set

9.6.

Test run

9.6.1.

Direction of rotation: check

40
5.
As soon as the pointer [2] moves to mark [3]: Stop turning and release setting
spindle.
The intermediate position setting in running direction CLOSE is complete.
6.
If you override the tripping point inadvertently (ratchet click is heard after the
pointer has rotated): Continue turning the setting spindle in the same direction
and repeat setting process.
1.
Move valve in direction OPEN to desired intermediate position.
2.
If you override the tripping point inadvertently: Move valve in opposite direction
and approach intermediate position again in direction OPEN (always approach
the intermediate position in the same direction as in later electrical operation).
3.
Press down and turn setting spindle [4] with screw driver in direction of the
arrow and observe the pointer [5]: While a ratchet click is felt and heard, the
pointer [5] moves 90° every time.
4.
As soon as the pointer [5] is 90° from mark [6]: Continue turning slowly.
5.
As soon as the pointer [5] moves to mark [6]: Stop turning and release setting
spindle.
The intermediate position setting in running direction OPEN is complete.
6.
If you override the tripping point inadvertently (ratchet click is heard after the
pointer has rotated): Continue turning the setting spindle in the same direction
and repeat setting process.
Perform test run after all settings previously described have been performed.
Valve damage due to incorrect direction of rotation!
If the direction of rotation is wrong, switch off immediately (press STOP).
Eliminate cause, i.e. correct phase sequence for cable set wall bracket.
Repeat test run.
1.
Move actuator manually to intermediate position or to sufficient distance from
end position.
2.
Set selector switch to position Local control (LOCAL).
3.
Switch on actuator in direction CLOSE and observe the direction of rotation:
with indicator disc: Step 4
without indicator disc: Step 5 (hollow shaft)
Switch off before reaching the end position.