Commissioning (basic settings)
9.
Commissioning (basic settings)
9.1.
Heat-up time for low temperature version
9.2.
Switch compartment: open
36
1.
Set selector switch to position 0 (OFF).
Information: The selector switch is not a mains switch. When positioned to 0
(OFF), the actuator cannot be operated. The controls' power supply is
maintained.
2.
Switch on the power supply.
Information: Please consider the heat-up time for ambient temperatures below
4 °F ( 20 °C).
3.
Perform basic settings.
Please note that for low temperature versions, the controls require a heat-up time.
This heat-up time is applicable in case the actuator and the controls are not live and
have cooled down to ambient temperature. Under these conditions and after
connection to the voltage supply, the following heat-up times must be complied with
prior to commissioning:
For 76 °F ( 60 °C) = 80 min.
Figure 32: Sketch illustrating the heat-up time
[t ]
Heat-up time in minutes
[ϑ]
Ambient temperature in °C (14, 4, 22, 40, 58, 76 °F)
The switch compartment must be opened to perform the following settings (options).
Flameproof enclosure, danger of explosion!
Risk of death or serious injury.
Before opening, ensure that there is no explosive gas and no voltage.
Handle cover and housing parts with care.
Joint surfaces must not be damaged or soiled in any way.
Do not jam cover during fitting.
SAEx 07.2
SAEx 16.2 / SAREx 07.2
SAREx 16.2
AUMA MATIC AMExC 01.1