SAEx 07.2
SAEx 16.2 / SAREx 07.2
AUMA MATIC AMExC 01.1
9.7.1.

Measuring range: set

Information
Activate setting mode
Set measuring range
SAREx 16.2
Table 13:
Short overview on push button functions
Push but-
Function
tons
[S1] + [S2]
→ press simultaneously for 5 s: Activate setting mode
[S1]
→ press in setting mode for 3 s: Set 4 mA
→ press in setting mode for 6 s: Set 0 mA
→ press in operation for 3 s: Switch on/off LED end position signaling.
→ touch in end position: Reduce current value by 0.02 mA
[S2]
→ press in setting mode for 3 s: Set 20 mA
→ press in operation for 3 s: Switch on/off LED end position signaling.
→ touch in end position: Increase current value by 0.02 mA
For measuring range setting, voltage must be applied at the position transmitter.
For output current verification, connect a test device for 0
points (+/ ) (for 2-wire systems, connecting a test device is required).
Both measuring ranges 0/4
be set.
During setting process, the measuring range (normal or inverse operation) is
assigned to the end positions by push button S1/S2 assignment.
For 2-wire systems, switch off <LED end position signaling> prior to setting the
measuring range.
Setting mode activating clears the setting in both end positions and sets the
output current to a value of 3.5 mA. After activation, both end values (0/4 mA
and 20 mA) need to be reset.
In case of inadvertent incorrect adjustment, the settings can always be reset
by renewed activation of the setting mode (simultaneous pressing of [S1] and
[S2]).
1.
Press both push buttons [S1] and [S2] and hold down for 5 seconds:
By pulsing double flashes, the LED indicates that the setting mode is correctly
activated:
For any other LED flash sequence (single/triple flashing): Refer to <Faults
during commissioning>.
2.
Operate valve in one of the end positions (OPEN/CLOSED).
3.
Set desired output current (0/4 mA or 20 mA):
for 4 mA: Hold down push button [S1] for approx. 3 seconds,
until LED is blinking slowly
for 0 mA: Hold down push button [S1] for approx. 6 seconds,
until LED is blinking fast
for 20 mA: Hold down push button [S2] for approx. 3 seconds,
until LED is illuminated
Information: For 2-wire systems read current values at test device.
4.
Operate valve into opposite end position.
The value set in end position (0/4 mA or 20 mA) does not change during travel
in setting mode.
Commissioning (basic settings)
20 mA and 20
0/4 mA (inverse operation) can
.
.
.
20 mA to measurement
43