9.8.1.
Potentiometer setting
Information
9.9.
RWG electronic position transmitter
Technical data
Setting components
SAREx 16.2
Figure 39: View on control unit
[1]
Potentiometer
Due to the ratio of the reduction gearing, the complete resistance range/stroke is not
always covered. Therefore, external adjustment (setting potentiometer) must be
provided.
1.
Move valve to end position CLOSED.
2.
Turn potentiometer [1] clockwise to the stop.
End position CLOSED corresponds to 0 %
End position OPEN corresponds to 100 %
3.
Turn potentiometer [1] slightly in opposite direction.
4.
Perform fine-tuning of the zero point at external setting potentiometer (for remote
indication).
Option
RWG electronic position transmitter records the valve position. On the basis of the
actual position value measured by the potentiometer (travel sensor), it generates a
current signal between 0
Table 15: RWG 4020
Data
Output current I
a
1)
Power supply U
V
Max. current consumption
Max. load R
B
Impact of power supply
Load influence
Temperature impact
2)
Ambient temperature
Transmitter potentiometer
1)
Power supply possible via: AC, AM controls or external power supply
2)
Depending on temperature range of the actuator: Refer to name tag
The RWG is housed in the actuator switch compartment. The switch compartment
must be opened to perform any settings. Refer to <Switch compartment: open>.
Setting is made via three potentiometers [1], [2] and [3].
20 mA or 4
20 mA.
3-wire and 4-wire systems
0
20 mA, 4
20 mA
24 V DC (18
32 V)
24 mA at 20 mA output current
600 Ω
0.1 %/V
600 Ω)
0.1 %/(0
76 °F to 176 °F ( 60 °C to +80 °C)
Commissioning (basic settings)
2-wire system
4
20 mA
14 V DC + (I x R
), max. 30 V
B
20 mA
(U
14 V)/20 mA
V
0.1 %/V
0.1 %/100 Ω
< 0.3 ‰/K
5 kΩ