Torque Switch Setting - AUMA SAEx 07.2 Manual

Multi-turn actuators
Hide thumbs Also See for SAEx 07.2:
Table of Contents

Advertisement

SAEx 07.2
SAEx 16.2 / SAREx 07.2
AUMA MATIC AMExC 01.1
9.3.

Torque switch setting

Information
SAREx 16.2
1.
Loosen screws [2] and remove cover [1] from the switch compartment.
2.
If indicator disc [3] is available:
Remove indicator disc [3] using a wrench (as lever).
Information: To avoid damage to paint finish, use wrench in combination with
soft object, e.g. fabric.
Once the set torque is reached, the torque switches will be tripped (overload protection
of the valve).
The torque switches may also trip during manual operation.
Valve damage due to excessive tripping torque limit setting!
The tripping torque must suit the valve.
Only change the setting with the consent of the valve manufacturer.
Figure 33: Torque measuring heads
[1]
Torque switching head black in direction CLOSE
[2]
Torque switching head white in direction OPEN
[3]
Lock screws
[4]
Torque dials
1.
Loosen both lock screws [3] on torque dials.
Commissioning (basic settings)