Process Data; Overview Of Signal Voltages; Table 19: Overview Of Signal Voltages - WAGO 750 Series Manual

I/o system 750 2ai resistor bridge (strain gauge), 2-channel analog input for resistor bridges (strain gauge)
Hide thumbs Also See for 750 Series:
Table of Contents

Advertisement

36
Process Image
4.2.1

Process Data

4.2.2

Overview of Signal Voltages

The following table provides an overview of all supported signal voltages.
The following sections contain detailed information about the individual signal
voltages. The information provided in the respective tables on the resolution of
the measured values and the raw value ranges yielded from this are based on
manufacturing scaling.

Table 19: Overview of Signal Voltages

Signal Voltage
Input deactivated
Bridge voltage U
Bridge voltage U
Bridge voltage U
Bridge voltage U
Bridge voltagU
Bridge voltage U
Reference voltage U
Reference voltage U
Reference voltage U
Reference voltage U
Manual
Version 1.0.0
Measurement
Range
Strain Gauge (Inputs 1 and 3)
(±15 mV)
−15 ...+15 mV
d
(±30 mV)
−30 ...+30 mV
d
(±60 mV)
−60 ...+60 mV
d
(±120 mV)
−120 ...+120 mV
d
(±240 mV)
−240 ...+240 mV
d
(±360 mV)
−360 ...+360 mV
d
Strain Gauge (Inputs 2 and 4)
(5 V)
+2.5 ...+5 V
ref
(±5 V)
−5 ...+5 V
ref
(±10 V)
−10 ...+10 V
ref
(±15 V)
−15 ...+15 V
ref
750-1491 2AI Resistor Bridge (Strain Gauge)
Representation
Two's Complement /
Amount Sign
Resolution
0,0006 mV
0,0012 mV
0,0024 mV
0,0048 mV
0,0096 mV
0,0144 mV
0.20 mV
0.20 mV
0.40 mV
0.60 mV
WAGO I/O System 750
Raw Value Range
−25000...25000
−25000...25000

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-1491

Table of Contents