Table 34: "Menu Items "Input X - WAGO 750 Series Manual

I/o system 750 2ai resistor bridge (strain gauge), 2-channel analog input for resistor bridges (strain gauge)
Hide thumbs Also See for 750 Series:
Table of Contents

Advertisement

64
Commissioning

Table 34: "Menu Items "Input X"

Parameter
Bridge voltage
Reference voltage
Smoothing
Number format
Input diagnosis
Diagnosis: Overflow This parameter can be used to switch diagnostics on/off for
Diagnosis:
Underflow
Manual
Version 1.0.0
750-1491 2AI Resistor Bridge (Strain Gauge)
Setting Option / Description
This parameter can be used to set the measuring range of
1)
the bridge voltage or deactivate the input.
Input
deactivated
±15 mV
*)
±30 mV
±60 mV
±120 mV
±240 mV
±360 mV
2)
This parameter can be used to set the measuring range of
the reference voltage or deactivate the input.
Input
deactivated
5 V (internal)
*)
±5 V (external)
±10 V (external)
±15 V (external)
This parameter can be used to configure the analog value
smoothing.
deactivated
*)
weak
medium
strong
This parameter can be used to configure the representation
of the process value on the fieldbus.
Twos
Complement
*)
Sign magnitude Amount/sign representation
This parameter can be used to switch diagnostics on/off.
Off
On
*)
an overflow.
Off
On
*)
This parameter can be used to switch diagnostics on/off for
an underflow.
Off
On
*)
WAGO I/O System 750
Measuring range selection of the bridge
voltage for the input. The input can also
be deactivated in this parameter. Then a
0x7FFF is delivered as process value
Measuring range selection of the
reference voltage for the input. The input
can also be deactivated in this parameter.
Then a 0x7FFF is delivered as process
value
Smoothing is switched off.
Weak analog value smoothing
Medium analog value smoothing
Strong analog value smoothing
Two's complement representation
Input diagnosis is switched off.
Input diagnosis is switched on.
Overflow diagnosis is switched off.
Overflow diagnosis is switched on.
Underflow diagnosis is switched off.
Underflow diagnosis is switched on.

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-1491

Table of Contents