Commissioning
For offset and gain correction, arbitrary reference values within the measurement
range can be entered as setpoints. Ideally, the reference values should be as
close as possible to the lower (offset correction) or upper (gain correction) full
scale value.
4.
Close the dialog. This saves the calibration instructions directly.
Therefore, it is not necessary to click the [Write] button.
After the calibration, the process values will correspond to the reference values
over the entire range.
The measuring circuits can be calibrated in the same way, independently of each
other.
The calibration process is performed on a input basis; therefore, before the
calibration process, be sure to select the corresponding input.
5.
Repeat the calibration for each input if necessary.
Note: If the calibration fails, the original calibration values are restored
Additional information on calibration
Detailed information about calibratiob can be found in Section "Calibrating
Measured Values!"