Figure 30-3 Dc Power Entry Module With Conduit Box - Cisco BPX-BXM-155-8DX Installation And Configuration Manual

Cisco bpx-bxm-155-8dx: user guide
Table of Contents

Advertisement

Replacing a DC Power Entry Module

Figure 30-3 DC Power Entry Module with Conduit Box

Conduit cover
Conduit connection
(customer supplied)
90 terminal lug
If a conduit box is used, remove it. Remove the ground screw above the middle terminal block
Step 6
connector (see Figure 30-3).
Remove the two standoffs on each side of the terminal block and pull the conduit box straight back. Set
Step 7
it aside. Do not try to remove the terminal block.
Loosen the two captive screws (at the bottom corners) holding the PEM. Loosen the two connector
Step 8
jackscrews adjacent to the finger pull.
Grasp the finger pull lip at the top of the PEM and pull the unit straight out.
Step 9
Replacement is the reverse of removal.
Step 10
Cisco BPX 8600 Series Installation and Configuration
30-6
O N
C B 1
O F F
screws
Conduit box
cover
O N
C B 1
O F F
(3 places)
U S E
C O N
C O P
D U C
P E R
T O R
S O N
L Y
U S E
C O N
C O P
D U C
P E R
T O R
S O N
L Y
+ R T
N
– 4 8 V
Release 9.3.0, Part Number 78-10674-01 Rev. D0, July 2001
Chapter 30
Replacing Parts