8
Mounting the Ceiling Tube to the Threaded Bolts of the Interface Plate
Figure 21: Mounting a ceiling tube
8.2
Mounting a ceiling tube
(See "Figure 21")
The Figure only shows a simplified representation of the flange⑥ with
ceiling tube to be mounted to the threaded bolts. Further components
pre-assembled to the flange⑥, such as the motor arm, extension arm,
cables, etc. are not represented.
Risk of parts falling off
Make sure that no-one is standing underneath the compo-
nents of the pendant system whilst it is being installed.
1.
Securely fasten the flange⑥ of the ceiling tube with motor arm
or the extension arm with motor arm
with motor arm
to a suitable lifting device and position it under
5
the threaded bolts M16① of the interface plate
NOTE – Position of the flanges on the Duo version
•
The flanges have a chamfered surface⑦ in order to ensure that they
can be mounted at the same height.
•
Mount the flanges such that the chamfered surfaces⑦ are aligned
towards each other as illustrated in the Figure.
2.
Insert the flange⑥ of the ceiling tube with motor arm
tension arm with motor arm
arm
into the 6 threaded bolts M16① of the interface plate
5
3.
Remove the previously attached adhesive or elastic tape from the
threaded bolts①.
4.
For each threaded bolt M16①, place 1 plastic insulating disc① (as
illustrated in the Figure) in such a way that the flat washer with an
external diameter of 34mm③ (see arrow in the detailed representa-
tion in the Figure) sits in the plastic insulating disc①.
5.
For each threaded bolt M16①, place 1 flat washer with an external
diameter of 34mm③, 1 spring disc④ and 1 hexagonal nut M16⑤.
6.
Component on the interface plate
•
Align the Single version as described in Chapter 8.3 on Page 38.
•
Align the Duo version as described in Chapter 8.4 on Page 40.
37
WARNING
or the XL extension arm
5
.
1
4
or the XL extension arm with motor
5
:
1
1568911, Edition 2019-04, Version 0
EN
4
or the ex-
.
1